Fire Test Reports – United States


All NOVAWALL fire tests are conducted according to the latest specimen mounting method ASTM 2573 07, included in the IBC and the IFC 2009 versions.

Important!

Results of ASTM E-84 Tests

 

System Type Flame Spread Smoke Developed Class Test Facility
1″ Square Edge with ⅛” Reveal System PDF 10 95 A HPVA, Reston, VA
1″ Square Edge with ¼” Reveal System PDF 15 250 A HPVA, Reston, VA
1″ Square Edge with ½” Reveal System PDF 20 300 A HPVA, Reston, VA
½” System with Tackable Micore PDF 20 135 A HPVA, Reston, VA
½” Square PDF 20 190 A HPVA, Reston, VA
¾” Weltless PDF 5 135 A HPVA, Reston, VA
1″ EcoTRACK System PDF 0 60 A HPVA, Reston, VA
1″ Square Edge and Midwall
with Formaldehyde Free Fiberglass PDF
25 350 A HPVA, Reston, VA
1″ Square System Green Fill(tm) Core PDF 40 450 B HPVA, Reston, VA
1″ Square System with Novawall Cotton Core PDF 45 450 B HPVA, Reston, VA
1″ Square System PDF 15 170 A VTEC, Bronx, NY
7/8″ Bevel System PDF 20 185 A HPVA, Reston, VA
2″ Square Edge Weltless Concealed PDF 15 250 A HPVA, Reston, VA
2″ Square Edge with Fire Retardant MDF PDF 15 175 A HPVA, Reston, VA
2″ Square Edge with Fire Retardant Plywood PDF 15 175 A HPVA, Reston, VA
4″ Square Edge PDF 15 125 A HPVA, Reston, VA
Novaspan10 System PDF 20 350 A HPVA, Reston, VA
Novaspan16 System PDF 25 200 A HPVA, Reston, VA
1″ Concealed Square Edge PDF 15 105 A HPVA, Reston, VA
1″ Novawall Radius Edge and Midwall Track 15 450 A HPVA, Reston, VA
1″ Novawall Bevel Edge and Midwall Track 10 200 A HPVA, Reston, VA

Results of NFPA 265 Method A

The NFPA 265 Test is referred to as the Corner Burn Test and is for wall coverings used in un-sprinkled spaces. In certain areas of the United States, this test is the only accepted test accepted as described in the Local Codes.

System Type Flame Spread (vertical) Flame Spread (horizontal) Pass/Fail Test Facility
Novawall 1″ Square Edge  – NFPA265 Test Report 6.0′ 5.0′ Pass Govmark, Farmingdale, NY